Battery Capacity Calculator
Enter the load power and the backup duration and, if needed, change the assumptions. All default parameters are marked as unconfirmed.
Your result
Fill in the form and press 'Calculate'.
Calculation example
Input data: Total power of critical loads: 1500 W; Required backup duration: 8 h; Simultaneity factor: 100 %; Allowed depth of discharge (DoD): 80 %; Inverter efficiency: 92 %; Reserve: 20 %; Capacity loss due to temperature: 10 %.
| Indicator | Low | Target | High |
|---|---|---|---|
| Nominal battery capacity, kWh | 20,13 | 27,17 | 36,68 |
| Usable energy, kWh | 11,59 | 15,65 | 21,13 |
The result is indicative and is not a power supply design or a promise of backup duration.
Missing data:
- Power factor (cos φ): Aggregate load
- Insufficient data: an engineering calculation is required.
Calculation module version: 1.0.0.
How it is calculated
- Energy = power × hours × duty factor.
- Usable energy = energy × (1 + reserve) / efficiency.
- Nominal capacity = usable energy / DoD / (1 − temperature) / (1 − ageing).
Assumptions (unconfirmed, replace with equipment data)
- An ageing reserve of 20% is used by default and is an unconfirmed assumption.
- DoD, efficiency and temperature loss values should be taken from the documentation of the specific equipment.
Limitations
- Battery voltage, charge and discharge currents, the number of modules and compatibility with the inverter are not calculated.
- The result is not a promise of backup duration.
Frequently asked questions
How does usable capacity differ from nominal capacity?
Usable capacity accounts for inverter losses and the reserve; nominal capacity also accounts for depth of discharge, temperature and ageing.
Can the default values be trusted?
They are unconfirmed assumptions for a first estimate. Replace them with the manufacturer data.